Date of this Version

6-1-2019

Document Type

Article

Abstract

The fast development of the residential sector regarding the additional integration of renewable distributed energy sources and the modern expansion usage of essential DC electrical equipment may cause severe power quality problems. For example, the integration of rooftop photovoltaic (PV) may cause unbalance, and voltage fluctuation, which can add constraints for further PV integrations to the network, and the deployment of DC native loads with their nonlinear behavior adds harmonics to the network. This paper demonstrates the smart integration of a DC microgrid to the neighborhood low-voltage distribution network (NLVDN). The DC microgrid is connected to the NLVDN through a three-phase voltage source inverter (VSI), in which the VSI works as a distribution static compensator (DSTATCOM). Unlike previous STATCOM work in the literature, the proposed controller of the VSI of the DC smart building allows for many functions: (a) it enables bidirectional active/reactive power flow between the DC building and the AC grid at point of common coupling (PCC); (b) it compensates for the legacy unbalance in the distribution network, providing harmonics elimination and power factor correction capability at PCC; and (c) it provides voltage support at PCC. The proposed controller was validated by Matlab/Simulink and by experimental implementation at the lab.